Ktl-icon-tai-lieu

DVP-SS2

Được đăng lên bởi hoangmark1989
Số trang: 19 trang   |   Lượt xem: 2517 lần   |   Lượt tải: 0 lần
2013-01-30

5011699703-S2S3

…………………………………………………………………  ENGLISH  ……………………………………………………………………

Thank you for choosing Delta DVP-SS2 series PLCs. DVP-SS2 series PLCs include
one 12-point PLC, and two 14-point PLCs. A DVP-SS2 series PLC provides various
instructions, and the size of the program memory in it is 8k steps. It is able to connect to
all DVP-S series extension modules, including digital I/O (max. 480 I/O points) and
analog modules (for A/D, D/A conversion and temperature measurement). 4 groups of
high-speed (10kHz) pulse output satisfy all kinds of applications. DVP-SS2 is small in
size, and can be install easily. Users do not have to install any batteries in DVP-SS2
series PLCs. The PLC programs and the latched data are stored in the flash memories.
 This instruction sheet only provides introductory information on electrical
specifications, general specifications, installation and wiring. For detailed information
on programming and instructions, please refer to “DVP-SS2 Operation Manual:
Programming”. For information about optional peripherals, please see individual
product instruction sheet enclosed with DVP-SS2.
 This is an OPEN TYPE device and therefore should be installed in an enclosure free
of airborne dust, humidity, electric shock and vibration. The enclosure should prevent
non-maintenance staff from operating the device (e.g. key or specific tools are
required to open the enclosure) in case danger and damage on the device may
occur.
 DO NOT connect input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power.
is correctly grounded in order to prevent
Make sure the ground terminal
electromagnetic interference. DO NOT touch any terminals when the power is
switched on.

 Product Profile
1 3.00

25.20

60.00

5

7

6

8

2
9
12
90.00

EXTENSION
PORT

10
11

3

4

4

13
14

3.00
[ Figure 1 ]

Unit: mm
1. POWER, RUN, ERROR indicator
2. RUN/STOP switch
3. I/O port for program communication (RS-232)
4. DIN rail clip
5. I/O terminals
6. I/O point indicator
7. Mounting hole for extension module

8. Nameplate
9. Extension port
10. DIN rail mounting slot (35mm)
11. Extension unit clip
12. RS-485 communication port
13. Mounting rail for extension module
14. DC power input

 Electrical Specifications
Model
Item

DVP14SS211R

DVP14SS211T

DVP12SS211S

24VDC (-15% ~ 20%)
Power supply voltage (with counter-connection protection on the polarity of DC input power)